Clamp On Ultrasonic Flow Meters
Due to the non-intrusive nature of the clamp-on technique, no mechanical parts need to be inserted through the pipe wall or to protrude into the flow system so there is no pressure drop (save energy), no moving parts (low maintenance), no leaks and no contamination.
Micronics Ultrasonic clamp on flow/heat meters
Order in the next
for guaranteed delivery tomorrow!
The U1000MKII-FM is an ultrasonic permanent/fixed clamp-on flow metering
solution for measuring flow rate and total flow with a volume pulse output and
optional Modbus or 4-20mA flow proportional output, which can be used as a
stand alone meter or as part of an integral management system.
The U1000MKII-HM is an ultrasonic clamp-on thermal, heat/
energy meter that uses ultrasound to measure flow rate and
PT100 temperature sensors to measure flow and return
temperatures. The U1000MKII-HM displays energy rate and
totalized energy with pulse output and communication options,
so it can be used as a standalone meter or as an integral part
of an a M&T or BEM’s system.
U1000MKII-FM – Fixed Ultrasonic Flow Meter
SPECIFICATION
Measurement Technique: Ultrasonic transit time method for flow
measurement.
Turn Down Ratio: 200:1
Accuracy: +/- 1% – 3% of flow reading for >0.3m/s (1 ft/s).
Flow Velocity Range: 0.1m/s – 10m/s (0.3 ft/s – 32 ft/s).
Pipe Range: Available in 2 options. 22mm to 115mm and 125mm to 180mm
OD. Note Pipe size is dependent on pipe material and internal diameter.
Water Temp Range: 0°C – 85°C (32°F – 185°F).
Pulse Output: Pulse or Frequency.
Pulse for Volume flow and Alarms.
Frequency for flow rate.
The pulse output can be configured as a loss of signal or low flow alarm.
4-20mA Output: Optional 4-20mA flow proportional output
Modbus Communication: Optional Modbus RTU slave, RS485 serial link
hardware layer. Modbus connection cable is 1m.
External Power Supply: 12V – 24V +/- 10% AC/DC at 7 watts per unit.
Optional plug in 12V power supply.
Electronics Enclosure: IP54.
Input/Output Cable: 5m x 6 core for power in, 4-20mA and pulse out.
U1000MKII-HM – Fixed Ultrasonic Heat/Energy Meter
with Modbus and Mbus Communication options
SPECIFICATION
Measurement Technique: Ultrasonic transit time method for flow measurement
and PT100 Class B 4 wire for temperature measurement.
Turn Down Ratio: 200:1
Heat Meter Standard: The Heat/Energy calculation is designed to comply with
EN1434 section 6.
Accuracy: +/- 1% – 3% of flow reading for >0.3m/s (1 ft/s).
Flow Velocity Range: 0.1m/s – 10m/s (0.3 ft/s – 32 ft/s).
Pipe Range: Available in 2 options. 22mm to 115mm and 125mm to 180mm OD.
Note Pipe size is dependent on pipe material and internal diameter.
Water Temp Range: 0°C – 85°C (32°F – 185°F).
Temperature sensors: Clamp-on PT100 Class B 4 wire, range 0°C – 85°C
(32°F – 185°F), resolution 0.1°C (0.18°F). Minimum delta T is 0.3°C.
Output: Pulse or Frequency.
Pulse for Volume flow and Energy in kWh(BTU).
Frequency for flow rate.
The pulse output can be configured as a loss of signal or low flow alarm.
Modbus Communication: Optional Modbus RTU slave, RS485 serial link hardware
layer. Energy, power, temperature and flow. Modbus connection cable is 1m.
Mbus Communication: Optional M-Bus.
External Power Supply: 12V – 24V +/- 10% AC/DC at 7 watts per unit.
Optional plug in 12V power supply.
Electronics Enclosure: IP54.
Input/Output Cable: 5m x 6 core for power in and pulse ou